Establish the actual source and operating mode
A chiller can contain fans, compressors and other parts with different spectra. Use sound power for the exact configuration, ideally including octave-band values supplied by the manufacturer.
A value for one operating mode may not apply to full load, night mode or defrosting. Select the relevant mode and name it clearly in the project note.
- LwA and available octave-band spectrum for each unit type.
- The number of units and their actual simultaneous operation.
- Height of the roof, unit, parapet and neighbouring windows.
- Airflow and installation conditions if louvres are being considered.
A roof and parapet do not screen every window equally
A unit behind a parapet may be partly screened from ground-floor windows while higher windows still see it directly. Do not assess location only in plan. The HvacCheck side sketch helps check heights and the direct sound path.
The map can use available elevation data and buildings. If the map is unavailable or does not match reality, enter distances and heights manually.
Compare barriers, louvres and enclosures
A panel barrier close to the unit can be effective if it extends above the direct source-to-window line and is long enough. HvacCheck accounts for diffraction around both ends of a straight barrier in simple and PRO modes.
Where free airflow is required, compare an acoustic louvre barrier or an enclosure with suitable openings. Louvre pressure drop is a separate assessment and does not by itself change the calculated noise level before or after mitigation.
- Compare several geometries, not just one panel type.
- For an enclosure, check permitted temperature, airflow and service clearances.
- For louvres, enter the actual branch airflow and installation arrangement.
Background noise, margin and professional assessment
Existing background noise can be entered at the window in dB(A). The calculator adds it energetically to the result before and after mitigation. An empty field leaves the original result exactly unchanged.
Large or critical installations also require checks for tonality, impulsiveness, vibration and the rules for the specific location. The calculator report is a clear input document, not a replacement for design or measurement.
Apply the guide to your own installation
Enter the units, window position and mitigation. The calculator compares noise before and after mitigation with the selected limit.
HvacCheck provides an indicative calculation based on ISO 9613-2. The result does not replace an acoustic study, on-site measurement or the manufacturer’s review of installation conditions.