Air conditioner noise: assess the outdoor unit and several units together

With air conditioning, the deciding factor is often not one small unit but several outdoor units operating together on a façade, terrace or roof. A proper assessment therefore includes every source that can run at the same time.

1

Why one catalogue number is not the whole answer

Sound power LwA describes the unit, while sound pressure at a window depends on distance, height, screening and reflections. LwA and LpA are not interchangeable.

With several units, levels are summed energetically. Two equally loud units produce approximately 3 dB more than one; the calculator therefore supports unit quantities and different types in PRO mode.

2

Data for an apartment building or office

Prepare data sheets for every unit and check whether sound power is stated for the same operating point. Include more distant roof units if they have direct sight of the window.

Mark windows of your own and neighbouring habitable rooms. For façade-mounted units, consider reflection from the wall behind the source and windows above the unit, which may be higher than the barrier.

  • LwA for each unit type and the number operating simultaneously.
  • Unit and window heights relative to a common level.
  • Distance to every assessed window.
  • Night or evening operation and existing background noise if available.
3

How to choose noise mitigation

A barrier is useful where it blocks the direct sound path to the window. Its ends must be long enough to prevent sound travelling around the sides. For a row of units, compare one shared barrier with measures at individual sources.

Louvres and enclosures are especially relevant where airflow also needs to be designed. HvacCheck compares the acoustic options; for louvres it separately reports pressure drop using available catalogue curves.

  • Do not obstruct air intake or discharge without the manufacturer’s approval.
  • Check service access and clear space around the units.
  • Compare before-and-after results at every important window.
4

When an indicative calculation is not enough

Buzzing, rattling, repeated starts or façade vibration can have causes other than overall sound power. These effects need inspection on the actual installation.

If the result is just below the limit, account for uncertainty and input quality. Unclear data sheets, tonal components or disputed situations require professional measurement and assessment.

Apply the guide to your own installation

Enter the units, window position and mitigation. The calculator compares noise before and after mitigation with the selected limit.

HvacCheck provides an indicative calculation based on ISO 9613-2. The result does not replace an acoustic study, on-site measurement or the manufacturer’s review of installation conditions.