Which data-sheet value you need
Look for sound power LwA in dB(A). It describes the source and is needed to compare units and calculate sound propagation. Sound pressure LpA is instead a value measured or calculated at a particular point and distance.
If the manufacturer gives only LpA, establish the measurement distance and installation conditions. HvacCheck provides a helper conversion to LwA for a unit freely standing on the ground, near a wall or in a corner. Without these conditions, conversion is not unambiguous.
- The exact model and operating point, not just the product range.
- Sound power LwA, or LpA with distance and measurement conditions.
- The number of units that can operate simultaneously.
- Evening and night operation, including higher-output modes.
Where and how to measure the location
Choose the window of a habitable room or another protected location as the assessment point. With several windows, assess each separately; the closest window may not be the worst if another has direct sight of the unit.
In the calculator, enter horizontal distances from the source to the barrier plane and from the barrier to the window. Source and window heights refer to a common 0 m level. When using the map, check the placed points and heights above terrain.
- Unit and window height above the common reference level.
- Actual obstacles, façades and possible reflections.
- Existing background noise if known; an empty field leaves the result unchanged.
Which mitigation options to compare
A solid panel barrier interrupts the direct sound path, but sound can travel over the top and around both ends. Its height, length and distances to the unit and window therefore matter.
An acoustic louvre barrier allows airflow while adding attenuation. An enclosure surrounds the unit and may provide greater attenuation, but must respect air intake and discharge, service access and the manufacturer’s instructions.
- First try a location with more distance or no direct sight of the window.
- Compare several barrier heights and lengths; a short barrier can lose performance through side paths.
- For louvres, also check pressure drop and the manually entered branch airflow.
- Do not select an enclosure without checking airflow and permitted installation clearances.
What the heat pump calculation does not resolve
Defrosting, tonal components, rattling and structure-borne transmission into the building may require separate assessment. Verify any quiet mode using manufacturer data, because it can change available output.
The result at a window is not confirmation of building-control or regulatory compliance. For a borderline result, complaint or complex setting, use the report as input to professional assessment and measurement.
Apply the guide to your own installation
Enter the units, window position and mitigation. The calculator compares noise before and after mitigation with the selected limit.
HvacCheck provides an indicative calculation based on ISO 9613-2. The result does not replace an acoustic study, on-site measurement or the manufacturer’s review of installation conditions.